THERMOELECTRIC WATER COOLING

A Peltier cooling module still depends on the appliance around it.

LL-08B is a complete 0.8 L thermoelectric water cooling module. It combines the cold tank, dual TEC devices, cold-side conduction, heat-pipe heat rejection, fan and two NTC sensors. The OEM appliance still determines supply, water interfaces, mounting and cabinet airflow.

A Peltier cooling module still depends on the appliance around it.
Selection takeaway

Treat airflow and stated test conditions as part of the cooling specification. A compact module cannot deliver its published result if the hot side cannot reject heat into the cabinet airflow.

1. Use the correct product terminology

LL-08B uses thermoelectric cooling, also called Peltier or TEC cooling. “Semiconductor cooling” may be used as a descriptive term. “Superconducting cooling” describes a different physical concept and should not be used for this product.

  • Preferred: thermoelectric cooling module
  • Accepted: Peltier cooling module or TEC cooling module
  • Avoid: superconducting cooling module

2. Understand the supplied thermal path

StageLL-08B componentIntegration meaning
Water side0.8 L insulated tank and cold-pipe conductionConnect the appliance water path to the published ports
Heat transferDual 12706 TEC devicesMatch the specified DC configuration and appliance control
Hot sideHeat-pipe condenser and forced-air fanKeep fan inlet and outlet unobstructed
SensingTwo B3950 / 10K NTC sensorsReview sensing and appliance control interfaces

3. Keep performance and conditions together

The published output is greater than 2 L/h of mixed water at 10°C or below, and greater than 3.2 L/h at 15°C or below.

  • Ambient temperature: 25°C
  • Inlet-water temperature: 25°C
  • Rated electrical input
  • Fan inlet and outlet unobstructed
  • First draw excluded from the hourly result
A different ambient temperature, inlet temperature, airflow resistance or draw pattern can change the appliance result and requires validation.

4. Information needed for an OEM review

  • Cabinet drawing and available 165×115×308 mm installation envelope.
  • Ambient and inlet-water temperature range.
  • Target cold-water temperature and draw volume over time.
  • DC 12 V or 24 V arrangement according to the TEC configuration.
  • Fan inlet, hot-air outlet and clearance from nearby heat sources.
  • Water connection, drain path, mounting holes and service access.
FAQ

Questions OEM teams ask during selection

Is LL-08B a bare Peltier device?

No. It is an assembled water cooling module containing the tank, dual TECs, cold-side conduction, heat-pipe heat rejection, fan and two NTC sensors.

Can the fan inlet or outlet be partly blocked?

The published condition requires unobstructed fan inlet and outlet. Any cabinet restriction should be evaluated in the target appliance.

Does the published output apply at every inlet temperature?

No. The published values are tied to 25°C ambient and 25°C inlet water, rated electrical input and the stated test sequence.

Review LL-08B against the real cabinet and draw pattern.

Provide the cabinet space, inlet temperature, target cold-water temperature, draw pattern, electrical supply and airflow arrangement.

Send project conditions